Sign In | Join Free | My isp.org.cn |
|
Brand Name : SIEMENS
Model Number : CPU 1516-3 PN/DP 6ES7516-3AN01-0AB0
Certification : CE
Place of Origin : Germany
MOQ : 1
Price : USD
Payment Terms : L/C, T/T
Supply Ability : 100
Delivery Time : 10-12Days
Packaging Details : 15,10 x 15,40 x 4,60
Memory : Up to 2 MB
Power Supply : 24V DC
Dimensions : 130 x 150 x 75 mm
Number Of Communication Modules : Up to 32
Number Of Technology Modules : Up to 32
Number Of Motion Control Axes : Up to 128
Number Of Digital Inputs : Up to 64
Number Of Analog Inputs : Up to 32
Number Of Analog Outputs : Up to 32
Number Of Digital Outputs : Up to 64
Cpu Type : S7-1500
Operating Temperature Range : -20°C to +60°C
SIEMENS PLC SIMATIC S7-1500CPU 1516-3 PN/DP 6ES7516-3AN02-0AB0CENTRAL PROCESSING UNIT WITH 1 MB
Product Introduction:
The SIEMENS PLC SIMATIC S7-1500 CPU 1516-3 PN/DP 6ES7516-3AN02-0AB0 is a central processing unit (CPU) designed for industrial automation applications. It belongs to the Siemens SIMATIC S7-1500 series, a family of high-performance programmable logic controllers (PLCs) renowned for their advanced functionality and reliability.
Product Information and Specifications:
- Model: CPU 1516-3 PN/DP 6ES7516-3AN02-0AB0
The CPU 1516-3 PN/DP features a powerful processor that enables fast and efficient execution of control programs. It supports various programming languages, including ladder logic, function blocks, and structured text, providing flexibility and ease of programming for complex control tasks.
In terms of memory capacity, the CPU 1516-3 PN/DP offers ample storage space for both program and data. While specific details were not provided in the query, typical configurations of the CPU include program memory ranging from 2 MB to 10 MB and data memory ranging from 1 MB to 5 MB. This memory capacity allows users to store their control programs and necessary data structures for the PLC's operation.
The CPU 1516-3 PN/DP is designed to operate in demanding industrial environments, delivering reliable and precise control for applications such as manufacturing, process control, and machine automation. It supports a wide range of communication interfaces, including PROFINET, PROFIBUS, and Ethernet, enabling seamless integration with other devices and systems in the automation network.
The CPU 1516-3 PN/DP is typically programmed and configured using Siemens' TIA Portal (Totally Integrated Automation Portal) software. The TIA Portal provides a comprehensive engineering environment for efficient programming, simulation, and diagnostics, ensuring easy development and maintenance of automation projects.
Product Attributes:
- Model: CPU 1516-3 PN/DP 6ES7516-3AN02-0AB0
- Processor: Powerful processor for fast and efficient execution of control programs
- Programming Languages: Supports ladder logic, function blocks, and structured text
- Memory Capacity: Ample storage space for program and data
- Communication Interfaces: Supports PROFINET, PROFIBUS, and Ethernet
- Engineering Software: Programmed and configured using Siemens' TIA Portal
- Suitable for: Manufacturing, process control, and machine automation applications
In summary, the SIEMENS PLC SIMATIC S7-1500 CPU 1516-3 PN/DP 6ES7516-3AN02-0AB0 is a high-performance CPU with advanced features, generous memory capacity, and extensive communication capabilities. It provides efficient and reliable control for industrial processes, making it well-suited for a wide range of industrial automation applications.
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
● Isochronous mode | Yes; Distributed and central; with minimum OB 6x cycle of 375 µs (distributed) and 1 ms (central) | |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated from version | V17 (FW V2.9) / V16 (FW V2.8) or higher; with older TIA Portal versions configurable as 6ES7516-3AN01-0AB0 | |
Configuration control | ||
via dataset | Yes | |
Display | ||
Screen diagonal [cm] | 6.1 cm | |
Control elements | ||
Number of keys | 8 | |
Mode buttons | 2 | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Mains buffering | ||
● Mains/voltage failure stored energy time | 5 ms | |
● Repeat rate, min. | 1/s | |
Input current | ||
Current consumption (rated value) | 0.85 A | |
Current consumption, max. | 1.1 A | |
Inrush current, max. | 2.4 A; Rated value | |
I²t | 0.02 A²·s | |
Power | ||
Infeed power to the backplane bus | 12 W | |
Power consumption from the backplane bus (balanced) | 6.7 W | |
Power loss | ||
Power loss, typ. | 7 W | |
Memory | ||
Number of slots for SIMATIC memory card | 1 | |
SIMATIC memory card required | Yes | |
Work memory | ||
● integrated (for program) | 1 Mbyte | |
● integrated (for data) | 5 Mbyte | |
Load memory | ||
● Plug-in (SIMATIC Memory Card), max. | 32 Gbyte | |
Backup | ||
● maintenance-free | Yes | |
CPU processing times | ||
for bit operations, typ. | 10 ns | |
for word operations, typ. | 12 ns | |
for fixed point arithmetic, typ. | 16 ns | |
for floating point arithmetic, typ. | 64 ns | |
CPU-blocks | ||
Number of elements (total) | 8 000; Blocks (OB, FB, FC, DB) and UDTs | |
DB | ||
● Number range | 1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999 | |
● Size, max. | 5 Mbyte; For DBs with absolute addressing, the max. size is 64 KB | |
FB | ||
● Number range | 0 ... 65 535 | |
● Size, max. | 1 Mbyte | |
FC | ||
● Number range | 0 ... 65 535 | |
● Size, max. | 1 Mbyte | |
OB | ||
● Size, max. | 1 Mbyte | |
● Number of free cycle OBs | 100 | |
● Number of time alarm OBs | 20 | |
● Number of delay alarm OBs | 20 | |
● Number of cyclic interrupt OBs | 20; With minimum OB 3x cycle of 250 µs | |
● Number of process alarm OBs | 50 | |
● Number of DPV1 alarm OBs | 3 | |
● Number of isochronous mode OBs | 3 | |
● Number of technology synchronous alarm OBs | 2 | |
● Number of startup OBs | 100 | |
● Number of asynchronous error OBs | 4 | |
● Number of synchronous error OBs | 2 | |
● Number of diagnostic alarm OBs | 1 | |
Nesting depth | ||
● per priority class | 24 | |
Counters, timers and their retentivity | ||
S7 counter | ||
● Number | 2 048 | |
Retentivity | ||
— adjustable | Yes | |
IEC counter | ||
● Number | Any (only limited by the main memory) | |
Retentivity | ||
— adjustable | Yes | |
S7 times | ||
● Number | 2 048 | |
Retentivity | ||
— adjustable | Yes | |
IEC timer | ||
● Number | Any (only limited by the main memory) | |
Retentivity | ||
— adjustable | Yes | |
Data areas and their retentivity | ||
Retentive data area (incl. timers, counters, flags), max. | 512 kbyte; In total; available retentive memory for bit memories, timers, counters, DBs, and technology data (axes): 472 KB | |
Extended retentive data area (incl. timers, counters, flags), max. | 5 Mbyte; When using PS 6 0W 24/48/60 V DC HF | |
Flag | ||
● Size, max. | 16 kbyte | |
● Number of clock memories | 8; 8 clock memory bit, grouped into one clock memory byte | |
Data blocks | ||
● Retentivity adjustable | Yes | |
● Retentivity preset | No | |
Local data | ||
● per priority class, max. | 64 kbyte; max. 16 KB per block | |
Address area | ||
Number of IO modules | 8 192; max. number of modules / submodules | |
I/O address area | ||
● Inputs | 32 kbyte; All inputs are in the process image | |
● Outputs | 32 kbyte; All outputs are in the process image | |
per integrated IO subsystem | ||
— Inputs (volume) | 8 kbyte | |
— Outputs (volume) | 8 kbyte | |
per CM/CP | ||
— Inputs (volume) | 8 kbyte | |
— Outputs (volume) | 8 kbyte | |
Subprocess images | ||
● Number of subprocess images, max. | 32 | |
Hardware configuration | ||
Number of distributed IO systems | 64; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET or PROFIBUS communication modules, but also by the connection of I/O via AS-i master modules or links (e.g. IE/PB-Link) | |
Number of DP masters | ||
● integrated | 1 | |
● Via CM | 8; A maximum of 8 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total | |
Number of IO Controllers | ||
● integrated | 2 | |
● Via CM | 8; A maximum of 8 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total | |
Rack | ||
● Modules per rack, max. | 32; CPU + 31 modules | |
● Number of lines, max. | 1 | |
PtP CM | ||
● Number of PtP CMs | the number of connectable PtP CMs is only limited by the number of available slots | |
Time of day | ||
Clock | ||
● Type | Hardware clock | |
● Backup time | 6 wk; At 40 °C ambient temperature, typically | |
● Deviation per day, max. | 10 s; Typ.: 2 s | |
Operating hours counter | ||
● Number | 16 | |
programming / cycle time monitoring / header | ||
● lower limit | adjustable minimum cycle time | |
● upper limit | adjustable maximum cycle time | |
Dimensions | ||
Width | 70 mm | |
Height | 147 mm | |
Depth | 129 mm | |
Weights | ||
Weight, approx. | 845 g |
![]() |
SIEMENS PLC SIMATIC S7-1500CPU 1516-3 PN/DP 6ES7516-3AN02-0AB0CENTRAL PROCESSING UNIT WITH 1 MB Images |